Inovonics EE1243 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Kommunikation Inovonics EE1243 herunter. Inovonics EE1243 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 3
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
5.21.14 06598A © Inovonics, 2014 - www.inovonics.com
EE1243 EchoStream
®
Smoke Detector
Transmitter
Installation Instructions
1 Overview
The EE1243 smoke detector is a wireless, battery powered photoelectric
smoke sensor. The sensor includes a built-in sounder for alarm alerts, a
visual status LED, a back tamper, and an Inovonics transmitter. The sensor
works as part of a security/fire alarm system and communicates with the
system control panel. Under normal (non-alarm) conditions, the LED
flashes once every eight seconds while the sensor monitors the
surrounding conditions. When the sensor detects smoke, the LED lights,
the built-in sounder beeps loudly, and an alarm signal is transmitted. The
smoke sensor is powered by the two included three-volt lithium batteries.
When the EE1243 detects an inactive smoke sensor a tamper message will
be transmitted.
1.1 Inovonics Wireless Contact Information
If you have any problems with this procedure, contact Inovonics Wireless
technical services:
E-mail: [email protected]
Phone: (800) 782-2709; (303) 939-9336
1.2 EE1243 External Components
Figure 1 EE1243 external components
Status LED: The LED indicates the status of the sensor as follows:
LED flashes every 8 seconds to indicate normal operation.
LED stays on when the sensor detects smoke, and is sending an
alarm.
LED stays off when maintenance is required.
Test/silence button: Test/silence is pressed to perform the sensitivity test,
as well as to silence the low battery chirp. The low battery chirp will resume
after 24 hours if the condition is not corrected.
1.3 EE1243 Internal Components
Figure 2 EE1243 internal components
1.4 What’s In The Carton
Two BAT604 Duracell DL123A lithium batteries
Two drywall anchors
Two mounting screws
Two frequency band selection jumpers
2 Installation and Startup
2.1 Installation Notes
These products are designed to be maintained by professional
security technicians
Products are tested for indoor use
All products should be manually tested weekly
2.2 Install Batteries
1. Turn the sensor housing counterclockwise fifteen degrees and detach it
from the mounting base.
2. Remove the battery compartment cover.
Figure 3 Remove the EE1243 battery compartment cover
3. Install the two three-volt batteries.
4. Replace the battery compartment cover
Note: A tamper message will transmit for approximately ten seconds while
the unit powers up after the installation of both batteries. If only one battery
is installed, the tamper message will transmit continuously.
2.3 Open the Housing
5. Using a small screwdriver to press the sensor cap release tab, apply
downward pressure and turn the cap about one inch counter-clockwise
to remove the cap..
Figure 4 Remove the sensor cap
6. Place both thumbs on either side of the optical chamber and push down
to detach the sensor housing.
Figure 5 Push down on the optical chamber
A LED B Test/silence button
A Low battery/CleanMe
selection pins
B EchoStream select
compatibility selection
pins
C Reset button
B
A
A
B
C
Battery
Compartment
Cover
Seitenansicht 0
1 2 3

Inhaltsverzeichnis

Seite 1 - Transmitter

5.21.14 06598A © Inovonics, 2014 - www.inovonics.comEE1243 EchoStream® Smoke Detector TransmitterInstallation Instructions1 OverviewThe EE1243 smoke d

Seite 2 - 4 Clean the EE1243

5.21.14 06598A © Inovonics, 2014 - www.inovonics.com 22.4 Enable EchoStream SelectTo meet ETSI requirements, Inovonics has developed a new line of EE

Seite 3 - 6 Specifications

5.21.14 06598A © Inovonics, 2014 - www.inovonics.com 3Note: The base will not fit properly if the batteries are not installed.10. Reattach the sensor

Kommentare zu diesen Handbüchern